TECHNICAL DATA
|
||||||||||||||||||||||||||||||||||||||||||||||||||
TracPipe
Reel Dimensions and Weights |
||
Omegaflex Part No |
Description | Weight kgs |
FGP-SS4-12-100 |
TracPipe DN12 x 30metres | 6.4
kgs |
FGP-SS4-12-250 |
TracPipe DN12 x 75 metres | 13.2
kgs |
FGP-SS4-15-100 |
TracPipe DN15 x 30 metres | 10.0
kgs |
FGP-SS4-15-250 |
TracPipe DN15 x 75 metres | 18.2
kgs |
FGP-SS4-22-100 |
TracPipe DN22 x 30 metres | 10.0
kgs |
FGP-SS4-22-250 |
TracPipe DN22 x 75 metres | 25.0
kgs |
FGP-SS4-28-180 |
TracPipe DN28 x 55 metres | 27.3
kgs |
FGP-SS4-28-300 |
TracPipe DN28 x 90 metres | 44.0
kgs |
FGP-SS4-35-150 |
TracPipe DN32 x 45 metres | 30.0
kgs |
FGP-SS4-35-250 |
TracPipe DN32 x 75 metres | 52.3
kgs |
FGP-SS4-40-150 |
TracPipe DN40 x 45 metres | 36.8
kgs |
FGP-SS4-40-250 |
TracPipe DN40 x 75 metres | 56.8
kgs |
FGP-SS4-50-150 |
TracPipe DN50 x 45 metres | 41.8
kgs |
AutoFlare®
Straight BSP (ISO 7-1 'R') Taper Fittings |
|||
Omegaflex Part No |
Description |
Weight kgs |
![]() |
FGP-FST-12 |
AutoFlare DN12 x 3/8" BSP |
0.20 |
|
FGP-FST-15 |
AutoFlare DN15 x 1/2" BSP |
0.20 |
|
FGP-FST-22 |
AutoFlare DN22 x 3/4" BSP |
0.25 |
|
FGP-FST-28 |
AutoFlare DN28 x 1" BSP |
0.30 |
|
FGP-FST-35 |
AutoFlare DN32 x 1.1/4" BSP |
0.70 |
|
FGP-FST-40 |
AutoFlare DN40 x 1.1/2" BSP |
1.00 |
|
FGP-FST-50 |
AutoFlare DN50 x 2" BSP |
1.60 |
|
AutoFlare®
Coupling |
|||
![]() |
Omegaflex |
Description |
Weight |
FGP-CPLG-12 |
Coupling DN12 |
0.15 |
|
FGP-CPLG-15 |
Coupling DN15 |
0.25 |
|
FGP-CPLG-22 |
Coupling DN22 |
0.35 |
|
FGP-CPLG-28 |
Coupling DN28 |
0.45 |
|
FGP-CPLG-35 |
Coupling DN32 |
0.93 |
|
FGP-CPLG-40 |
Coupling DN40 |
1.50 |
|
FGP-CPLG-50 |
Coupling DN50 |
2.10 |
|
TracPipe
Tees |
|||
Omegaflex |
Description |
Weight |
|
FGP-TF15-T15 |
Tee DN15xDN15xDN15 |
0.50 |
|
FGP-TF22-T22 |
Tee DN22xDN22xDN22 |
0.75 |
|
FGP-TF28-T28 |
Tee DN28xDN28xDN28 |
1.00 |
|
FGP-TF22-T15 |
Tee DN22xDN22xDN15 |
0.75 |
|
FGP-TF28-T15 |
Tee DN28xDN28xDN15 |
1.00 |
|
FGP-RT-1001DN |
Tee DN28xDN22xDN15 |
1.00 |
|
FGP-RT-1002DN |
Tee DN28xDN22xDN22 |
1.00 |
|
FGP-RT-752DN |
Tee DN22xDN15xDN15 | 0.75 |
|
TracPipe
corrugated stainless steel tube to BS 7838 |
||||||||||
| Discharge in a straight corrugated stainless steel tube with 1.0 mbar differential pressure between the ends, for gas of relative density 0.6 (i.e. natural gas), (when air =1), and with 2.5 mbar differential for gas of relative density 1.5 (i.e. propane) | ||||||||||
| TracPipe Size |
Length
of pipe Meters |
|||||||||
| 3 | 6 | 9 | 12 | 15 | 20 | 25 | 30 | 40 | 50 | |
| DN | Discharge - cubic meters per hour | |||||||||
| 12 | 1.5 | 1.0 | 0.85 | 0.82 | 0.69 | 0.52 | 0.41 | 0.34 | ||
| 15 | 2.9 | 1.9 | 1.5 | 1.3 | 1.1 | 0.95 | 0.92 | 0.88 | 0.66 | 0.52 |
| 22 | 8.7 | 5.8 | 4.6 | 3.9 | 3.4 | 2.9 | 2.5 | 2.3 | 2.0 | 1.78 |
| 28 | 18 | 12 | 9.4 | 8.0 | 7.0 | 5.9 | 5.2 | 4.7 | 4.0 | 3.6 |
| 32 | 28.8 | 19.8 | 15.3 | 13.5 | 11.7 | 9.9 | 8.5 | 7.6 | 6.5 | 5.7 |
| 40 | 48.6 | 33.3 | 26.1 | 22.5 | 19.8 | 17.1 | 15.3 | 13.5 | 11.7 | 10.8 |
| 50 | 110 | 75 | 60 | 50 | 42 | 35 | 32 | 28 | 25 | 22 |
| Note: When using this table to estimate gas flow in TracPipe of a known length, this length should be increased by the values for every bend and tee, given in the Design & Installation Guide (see Downloads). | ||||||||||
Life
Expectancy |
Life Expectancy – 25/06/01 |
| TracPipe corrugated stainless steel semi-rigid pipe and associated fittings for low-pressure gas pipework – SAMPLE SPECIFICATION. |
|
GAS PIPING The gas piping material shall be Corrugated Stainless Steel Semi-rigid pipe Kitemarked to British Standard BS 7838 and installed in accordance with British Standards BS 6891, (2nd family gases), or BS 5482:Part 1, (3rd family gases),
in domestic premises, or in accordance with the Institution of Gas Engineers
publication IGE/UP/2 in other premises.
The stainless steel tubing should not be annealed after forming to ensure maximum crush resistance, and the attachment fittings must have a metal-to-metal seat to accomplish gas sealing. Elastomer seal rings or fibre gaskets are not permitted in the tubing to fittings sealing mechanism. A non-metallic jacket, coloured yellow ochre, and marked ‘GAS’, of non-halogenated, fire and smoke retardant polyethylene shall be used. Polyvinyl chloride (PVC) is not permitted as a jacket material. Where piping penetrates floor slabs evidence of a minimum 2 hour fire rating is required for the gas piping material. The gas piping material shall satisfy the requirements in BS 6891 for sleeved pipe, such that the piping can pass through unventilated voids, without joins, whilst maintaining its sleeved integrity. For timber frame housing, (refer to IGE/UP/7), the sleeving must be maintained, as above, without joins, where the pipework passes through unventilated voids in the construction. (Type TracPipe semi-rigid gas piping, available from
OmegaFlex Limited, FGP-076 UK March 2004 |